Will a System Sensor AP device work with FleX-Net V11?

While FleX-Net V11 does not support Advanced Protocol, several System Sensor devices are now equipped with AP addressable rotary switches. The devices will continue to operate in ‘CLIP’ mode, provided that the address remains within a value of 1 through 99. If an AP device is addressed outside the range 1 through 99 and connected to an earlier than V12 panel, that device will be treated by the panel as an ‘unconfigured’ device at address 00 regardless of the actual code wheel setting.

Please note that some devices such as the MIX-COSAP will only operate in AP mode. Please refer to the FleX-Net Device Compatibility Guide for further information LT-1023 Device Compatibility Guide.


Was this answer helpful to you?


Yes (1)    No (0)

Thank you! We will use your feedback to improve our frequently asked questions.
Thank you! We will use your feedback to improve our frequently asked questions.

Please contact Technical Support directly if you need further assistance.




GO BACK