- Listed to UL 864, 9th edition
- Integrated UDACT/Digital Communicator on select models
- 2 line by 20 character back-lit LCD display
- Front panel and PC programmable
- Remote upload/download capabilities
- Class “B” (Style “B”) initiating circuits,configured as Class “A” (Style “D”) using a Class “A” converter module
- Initiating circuits may be configured as Alarm, Verified Alarm, Waterflow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Monitor and Trouble-Only
- Audible signals configured for Steady, Temporal Code, California Code and March Time
- Indicating Circuits configurable as Silenceable or Non-Silenceable for both signals and strobes
- Built-in sync strobe protocols: Mircom, Amseco, System Sensor, Gentex, Faraday and Wheelock
- Relay contacts for Common Alarm, Auxiliary/Alarm (Disconnectable), Common Supervisory and Common Trouble
- Configurable Signal Silence Inhibit, Auto Signal Silence and One-Man Walk Test
- Subsequent Alarm, Supervisory, and Trouble operation
- RS-485 Interface for Remote LED Annunciators,
- Interface for a Remote Trouble Indicator (RTI)
- 200 event alarm log
- 5 Amp Power Supply
- Optional modules for additional internal relay circuits and City Tie/Polarity Reversal
Order Information
FA-301-12DDR
Twelve Zone LCD Display Fire Alarm Control Panel with built-in UDACT/Digital Communicator
FA-300TRB
Black Semi-Flush Trim Ring for FA-300-6 Enclosures
FA-UNIV-TRB
Black Universal Semi-Flush Trim Ring
FA-300-DF
Dead Front for FA-300-6DR/FA-300-6DDR
FA-301-DF
Dead Front for FA-301-12DDR