Yes, it is important and required as per NEC as well as FCC regulations. The telephone access unit should and must be grounded to the same communication bond point as the Building’s communication equipment. A confirmatory test to determine if the communication bond is the same ground point as the telephone ground is by measuring the voltage ( in ONHK mode)between the Tip and the equipment ground. The potential between the two points should be as low as possible ( 0>x<275-300mV).
Privacy Overview
This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.