Dear Valued Partner
The V2.0.3 update applies to the FleXNet FX-4000N Series Product line. All enhancements and updates introduced in V2.0.3 are outlined within this document.
This update is intended to provide new features and enhancements only.
This means existing systems operating on older versions are not required to update to this version unless the additional features introduced are needed or required. For component replacement or servicing of existing systems, components that contain newer software should be downgraded to match the existing system software. Access to older software versions is provided by contacting Mircom Applications Group at [email protected].
FleXNet V2.0.3 Compatibility Table
| Software # | Part Description | Platform / Part Number | Earliest Compatible Assembly/Version |
| SO-350 | Master CPU | FX-4000N | MD-871A (V2.0.3) |
| Network Communication Card (ARCnet) | FNC-2000 | MD-881 | |
| SO-355 | Audio Controller CPU | ANC-4000 | MD-888A (V1.0.79) |
| SO-351 SO-461 SO-480 SO-493 | Remote Annunciator (4×20) CPU Remote Annunciator Graphic (24×40) CPU Colour Main Display/Remote Annunciator (24×40) CPU | RAXN-4000LCD RAXN-4000LCDG (Obsolete) RAXN-4000LCDGC | MD-942 (V1.0.32) MD-992 MD-1355 (V1.2.3), MD-1356, MD-1357 |
| SO-353 SO-352 SO-510 | Quad Loop Controller Mother Card (Isolated) CPU: MGC Protocol Quad Loop Controller Daughter Card CPU: MGC Protocol Quad Loop Controller Mother Card (Isolated) CPU: AP/CLIP Protocol Quad Loop Controller Daughter Card CPU: AP/CLIP Protocol Single Loop Adder Card (Isolated) CPU | ALCN-960MISO ALCN-960D ALCN-4792MISO ALCN-792D ALCN-240ISO | MD-1218 (V1.0.94) MD-1219 MD-1076 (V1.0.75) MD-1003 MD-1440 (V1.2.53) |
| SO-296 | Digital Alarm Communicator | UDACT-300A | MD-802 (V3.0.25) |
| SO-229 | Intelligent Booster Power Supply | INX-10A, INX-10AC | MD-950 |
| MSW-046 | MGC Fire Detection and Mass Notification Configurator | Microsoft Windows 11 | V2.0.3 |
| MSW-035 | Open Graphic Navigator | OPENGN-PC-UL OPENGN-PC-NUL | V3.6.0 |
| SO-439 | Audio Controller CPU | ANC-6000 | MD-1267 (V1.0.9), REV E |
| SO-437 | Amplifier, 25V, 4 x 25W; Amplifier, 70V, 4 x 25W | QAD-6425-25, QAD-6425-70 | MD-1276, MD-1278 REV C (V1.27) |
| SO-317 | Power Management Module | QPS-6650 | MD-1274 (V1.7.22) REV D |
| SO-436 | Communication Card Assy | QCC-6000 | MD-1280 (V1.78) REV G |
| SO-318 | Network Master Microphone Control Module | QMP-6101NV | MD-1279 (V1.0.19) REV D |
Firmware Update Recommendations
As of date code 2626, production of the FleXNet product line and components will begin with FleXNet firmware, V2.0.3. This change is to ensure the most current updates and enhancements are provided to new and existing systems.
Earlier produced product shipping will require the upgrade.
Ideally, this update is intended for new system installations where final testing and verification has not yet been completed. For existing systems, the following recommendations should be considered.
This update may be implemented on systems currently operating on older FX-4000 FleXNet series software.
This update is intended for use on systems currently operating with FleXNet FX-4000 software [V1.12.XX to V1.15.XX]. Software changes should be properly assessed, and appropriate retesting/verification should be completed in accordance to local governing standards and codes.
This update is not recommended for systems currently operating older FleXNet series software V10.X.XX, or V11.X.XX, V12.X.XX without Mircom application team support.
The enhancements and changes are listed and explained throughout this document. Ensure that this document is carefully reviewed in its entirety
Plan the update and retesting according to all applicable national and local requirements
Review the system configuration following the update to ensure no unintended changes or modifications have occurred.
Where applicable, test all system operations which may be affected following the system update.
If you have any questions or concerns, please visit the Mircom Technical Support Forum, or contact the Technical Support Department directly.
Feature Additions & Enhancements in V2.0.3
Major Enhancements
- Version V2.0.3 is a major functional update over V1.15.602, focusing on:
- Improved backward compatibility and handling of legacy configuration files from older configurator versions.
- Configurator backward compatibility enhancements make it safer and easier to use existing job files and legacy panel configurations when upgrading to the V2.0.3 firmware line.
- Improved parsing of legacy configuration files
- Enhanced support for configuration files originally created on V1.15.602 and earlier.
- More tolerant handling of missing or deprecated fields; system now applies sensible defaults where appropriate instead of rejecting the file.
- Introduction of smoke device dirtiness monitoring and related event/reporting improvements. Enables clearer messaging to customers and service partners
- System can now indicate when smoke detectors are dirty or trending dirty, reducing nuisance alarms and optimizing maintenance visits.
- Each device will now report dirtiness level, panel service data, Mircom and system sensor devices both AP and CLIP
- Provide earlier and clearer visibility into smoke detector contamination (“dirtiness”), to support maintenance planning and reduce nuisance conditions.
- Upgrade/downgrade process – Introduced new firmware file extension to replace old format.
- Non-Flashing (NF) flag applied specifically to each device selected.
- Enhancements made when devices are set up as non-latching SUPV, to replace smoke alarms
- Improved network synchronization between panels
- Dirty detector trouble comes in at 80% for Mircom and System Sensor detectors
Major Features
- Allowed mimicking of “Zone Switch” virtually when using Open GN
- Added ability for Open GN to send synchronized event reporting to current panel data.
- Ability to forcefully turn on/off outputs directly from Open GN when utilized as control panel.
- Ability to retrieve event logs via configurator
Minor Enhancements
- Improved activation time for MIX-4000 series control modules
- Added support for zone reporting when using OpenGN
- Improved phone LED status annunciation indicators related to remote phone
- Enhanced event buzzer processing
- Event reporting on 6000 amplifiers improved
- Enhancements to panel reporting and description for audio fail
- Enhanced processing of events through MGD’s
- Added support for future LED annunciator
- Enhanced bypass command, bypass trouble stays within its group
- Added node control group
- Node control active timeout default set to 60min
Minor Features
- Improved FX-4000 printer port communication now supports handshake ability
- Added ability to utilize input module as a remote signal silence contact, while shorted signal silence status is executed to panel. When short is removed, signal silence is also removed.
- Ability for walk test countdown timer to be displayed on main LCD screen providing cost savings and flexibility on monthly inspections
- Improvement to walk test device activation handling
- Added INX-10A as a drop in template item to the configurator
Please reference this technical bulletin “TIB-FAP-25-001” when requesting an RMA with Customer Service.
As always, we appreciate your business and your understanding. If you have any questions or concerns, please contact the Application Group at [email protected].
Best Regards,
Mircom Product Management