- Verify that the card encryption type is checked off within the configurator access point’s configuration;
- Ensure that the board’s signal ground is stable;
- Ensure that the DATA0 and DATA1 is properly connected;
- Ensure that the card reader cable is shielded and properly grounded to a separate communication ground away from the board’s signal ground point;
- Ensure that the card reader is fully functional;
- Ensure that the power supply for the card reader is measured at 12 VDC (referenced the “common” signal ground when connected and not below 12 VDC);
- Ensure that the Card operates at the same frequency as the card reader;
- Ensure that the card reader’s cable is less than 350-450 ft in length; and
- Ensure that the card reader cable is not running alongside very high current draw loads.
Privacy Overview
This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.