Set the date/time for the panel to today’s time and date from the monitoring section; The unit did not receive its full configuration file. Individually send the full file to... read more →
Controller registries of last update entries are not registering- communication issue. Verify that you properly connected the RS485 line to each panel units and that no lines are crossed; Ensure... read more →
Use dipswitch setting on back of the HUBs to RS485 configure the HUBs, press refresh; NOTE: Use dipswitches for the HUBS to organize the RS485 HUB addresses;
This is likely caused by Line Noise. To fix this, check the following: Verify that all units have proper RS485 connections and that no stubs are used on the RS485... read more →
Ensure that the Card Access panel has a TX3-IP module board installed on the main control board; Connect the panel to the network; Port forward the panel’s IP address and... read more →
Verify Hub RS485 communication with the TX-CX-A-8 panel. Light indicator should be double green flashing, (indicating communicating with Lockset and controller); - If previous is true, then relocate the lockset... read more →